HOMEPRODUCTSBS50288-7 CABLE

 

 

EN 50288-7 Cables


APPLICATION :

EN 50288-7 unarmoured LSZH sheathed cables are generally use for indoor installation and suitable for wet and damp areas. Generally, EN 50288-7 cables are used within industrial process manufacturing plants for communication, data and voice transmission signals and services. Also used for the interconnection of electrical equipment and instruments, the LSZH sheath can reduce toxic smoke and fume emission.

STANDARDS :

RE-2Y(St)Y 90°C / 300 V

Basic design to EN 50288-7

FIRE PERFORMANCE :

Flame Retardance (Single Vertical Wire Test) EN 60332-1-2; IEC 60332-1-2; BS EN 60332-1-2; VDE 0482-332-1; NBN C 30-004 (cat. F1); NF C32-070-2.1(C2); CEI 20-35/1-2; EN 50265-2-1*; DIN VDE 0482-265-2-1*
Reduced Fire Propagation(Vertically-mounted bundled wires & cable test) EN 60332-3-24 (cat. C); IEC 60332-3-24; BS EN 60332-3-24; VDE 0482-332-3; NBN C 30-004 (cat. F2); NF C32-070-2.2(C1); CEI 20-22/3-4; EN 50266-2-4*; DIN VDE 0482-266-2-4
Halogen Free IEC 60754-1; EN 50267-2-1; DIN VDE 0482-267-2-1; CEI 20-37/2-1 ; BS 6425-1*
No Corrosive Gas Emission IEC 60754-2; EN 50267-2-2; DIN VDE 0482-267-2-2; CEI 20-37/2-2 ; BS 6425-2*
Minimum Smoke Emission IEC 61034-1&2; EN 61034 -1&2; DIN VDE 0482-1034-1&2; CEI 20-37/3-1&2; EN 50268-1&2*; BS 7622-1&2*
No Toxic gases NES 02-713; NF C 20-454
Sunlight Resistance UL 1581 section 1200
Oil Resistance ICEA S-73-532**

Note: Asterisk * denotes superseded standard, **Test temperature +60°C, duration 4h. Retention: min 60% of tensite strength/min.60% of elongation.

VOLTAGE RATING :

300V

CABLE CONSTRUCTION :

Conductor: Annealed copper solid or plain copper stranded to IEC 60228 Class 2.

Insulation: PE compound, EN 50290. 2-23.

Pairs: Two insulated conductors uniformly twisted together with a lay not exceeding 100mm

Binder tape: PETP transparent tape

Overall Screen: Aluminium/polyester tape is applied over the laid up pairs metallic side down in contact with tinned copper drain wire, 0.5mm² Outer Sheath: Thermoplastic LSZH compound type LTS3 as per BS 7655-6.1 (Thermosetting LSZH compound typeSW2-SW4 as per BS 7655-2.6 can be offered.). UV resistance, hydrocarbon resistance, oil resistance, anti rodent and anti termite properties can be offered as option.

COLOUR CODE :

Insulation: Black / White, continuously numbered on white core(1, 2..)for multipair.

Outer Sheath: Black or blue for intrinsically safe systems

Physical AND THERMAL PROPERTIES :

Temperature Range During Operation (Fixed State): -30°C – +90°C

Temperature Range During Installation (Mobile State): -5°C – +50°C

Minimum Bending Radius:7.5 X Overall Diameter

Electrical PROPERTIES :

Conductor Area Size mm 2 0.5 0.75 1.0 1.3 1.5
Insulation thickness (nominal) mm 0.35 0.38 0.4 0.45 0.45
Conductor resistance (20°C)  Ω/km 36.7 25 18.5 14.2 12.3
Insulation resistance (20°C) MΩ.km(Min.) 5000
Mutual Capacitance (1 kHz) pF/m(Max.)  
  ≤ 4 pairs 90 90 90 102 102
  all other pairs 75 75 75 85 85
Capacitance unbalance(1 kHz) pF/500 m (Max.) 500
Inductance mH/km (Max.) 1
L / R (ratio) (max.) μH/Ω 25 25 25 40 40
Operating voltage Urms V 300
Test Voltage Core to Core V 1500
Core to Screen V 1500

CONSTRUCTION PARAMETERS :

Caledonian Cable Code RE-2Y(St)HSWAH
No. of Pairsx2 xCross Section Nominal Insulation Thick
-ness
Nominal Inner Sheath Thick
-ness
Nominal
Overall Diameter Over Inner Sheath
Nominal Armour Wire Diameter Nominal Outer Sheath Thick
-ness
  No.x2xmm2 mm2 mm mm mm mm

RE-2Y(St)HSWAH 1P0.5

1x2x0.50

0.35

0.8

5.2

0.9

1.3

RE-2Y(St)HSWAH 1P0.75

1x2x0.75

0.38

0.8

5.6

0.9

1.3

RE-2Y(St)HSWAH 1P1.0

1x2x1.0

0.40

0.9

6.3

0.9

1.3

RE-2Y(St)HSWAH 1P1.3

1x2x1.3

0.45

0.9

6.8

0.9

1.3

RE-2Y(St)HSWAH 1P1.5

1x2x1.5

0.45

0.9

7.1

0.9

1.3

Note : Other conductor sizes & core configurations are available upon request